Technical Specifications
| Gas Detected | Combustible gas, toxic gas |
| Detection Range | (0% to 100%) LEL |
| Resolution Ratio | 1% LEL |
| Measurement Error | Full Scale ± 3% LEL |
| Status Indication | LCD |
| Sampling Mode | Natural diffusion |
| Response Time | T 90 s< 15 s |
| Power | DC 24 V ± 10% |
| Output Signal | 4 mA to 20 mA or RS 485 |
| Explosion Proof Grade | Exd ⅡC T 6 Gb |
| Ingress Protection | IP 66 |
| Size | 5.55 in × 7.007 in × 4.92 in (141 mm × 178 mm × 125 mm) |
| Weight | ≤7.71 lb (≤3.5 kg) |